User Manual

Rockwell Automation Publication 1756-UM005B-EN-P - January 2013 143
Appendix F
Module Revision History
Series A versus
Series B Firmware
If you have a series A module, you can upgrade the modules firmware to install
the same features that are available on the series B module. Any module that uses
firmware revision 3.005 and later has a series B designator. Series A modules that
are upgraded to revision 3.005 or later also have a series B designator.
Archiving Enhancement with Revision 3.005 and Later
Archiving is provided in firmware revision 3.005 and later. Because it is not
dependent on specialized module hardware, any high-speed analog module can
be updated to perform this function. For more information about this function,
see Archiving
on page 38.
Corrected Anomaly with Revision 3.005 and Later
The following anomaly is corrected in firmware revision 3.005 and later.
CORRECTED: When the high-speed analog module, series A, is used in a
system where its connection is through a 1756-EN2T module, I/O connections
cannot complete.
Upgrade the high-speed analog module to series B, firmware revision 3.005, to
enable the proper I/O connection.
Topic Page
Series A versus Series B Firmware 143
Series B Modules as Direct Replacements for Series A Modules 144
Install Series B Firmware 144