Installing the 1756-HYD02 Module
What This Chapter Contains
This chapter describes how to install the 1756-HYD02 module.
The 1756-HYD02 module mounts in a ControlLogix chassis and uses a
removable terminal block (RTB) to connect all field-side wiring.
Before you install your module, make sure you:
• install and ground a ControlLogix chassis and power supply.
• order and receive an RTB, and its components, for your application.
For more information on all the ControlLogix chassis and power supplies, see
the ControlLogix Selection Guide, publication
1756-SG001
.
Note the Power
Requirements
This module receives power from the 1756 chassis power supply and requires
two sources of power from the backplane:
• 700mA at 5.1V
• 2.5 mA at 24V
Add this current to the requirements of all other modules in this chassis to
prevent overloading the backplane power supply.
For information about: See page:
Installing the Module 14
Keying the Removable Terminal Block 15
Connecting Wiring 16
Assembling The Removable Terminal Block and
the Housing
23
Installing the Removable Terminal Block 26
Removing the Removable Terminal Block 28
Removing the Module from the Chassis 29