8. Enter Connection Parameters exactly as shown in the example below.
9. Check Open Module Properties to access additional dialog boxes to
enter information.
10. Click OK.
The Module Properties dialog box appears in the Connection tab.
11. Use the default RPI value and check Inhibit Module.
12. Click OK.
13. On the Controller Organizer, right-click I/O Configuration and choose
New Module.
Add a 1756-HSC module and assign it to an unused chassis slot in your
I/O Configuration tree.
This module will not be used, but the configuration of this profile will
aid later in the configuration of the generic module.
IMPORTANT
The generic connection works only with the matching
Assembly Instance and Size parameters listed above for
the input, output, and configuration settings.