Manual

Rockwell Automation Publication 1756-UM007C-EN-P - November 2011
94 1756-HSC Module History
1756-HSC Profile Overview
There are three profiles available for programming your 1756-HSC module
depending on your module’s firmware, software, and the desired functionality.
As shown in the table on
page 93
, you will use either a:
Full profile
Thin profile
Generic profile
Full profile support, for software versions 15 and later, include separate
Counter and Output Configuration tab dialog boxes that make it easier to
enter 1756-HSC operational data via a user-interface that provides error
checking and user-friendly data entry. See
Chapter 5
for configuring a module
with a full profile.
This section describes procedures for using a generic profile and modifying
tags with a thin profile.
Software versions prior to 15 do not include a user-interface that provides
error checking and user-friendly data entry. Instead, configuration tags have to
be manually entered during the initial set-up. This is referred to as a
thin profile.
A generic profile lets a prior software version use the functionality that’s
available only for the latest software. For example, a 1756-HSC module, with
software version 13, could use a generic profile to gain the output
functionality, available in software version 18, that lets you modify the outputs
in real-time by changing the rollover and preset values in the
output tags.
A generic profile will create non specific tags, with a name related to the
modules slot location. The tag names created will not reference any specific
1756-HSC module terminology.
IMPORTANT
To download firmware revisions for your module, go to
http://www.rockwellautomation.com/support
and choose
Downloads.
Do not backflash your modules firmware from firmware
revision 3.x to 2.x or 1x. Attempting to backflash or downgrade
a module’s firmware from 3.x to 2.x or 1x will irreversibly
damage the module.
1756-HSC modules at firmware revision 2.x or 1x cannot be
flash upgraded to any firmware revision 3.x because 3.x
modules have a hardware update.