User Manual

Rockwell Automation Publication ENET-IN002F-EN-P - January 2014 93
Appendix B
1768 EtherNet/IP Module Status Indicators
The 1768-ENBT and 1768-EWEB EtherNet/IP communication modules
support these status indicators. This graphic shows the front of the module for
the listed modules.
LINK
NET
OK
LINK
NET
OK
1
4
2
3
Table 3 - 1768-ENBT, 1768-EWEB EtherNet/IP Module Status Indicators
Number Status Indicator Description Status State
1 Module Status Display Alphanumeric display that scrolls messages. For
example, when a module is operating normally, the
display scrolls the modules IP address.
N/A N/A
2 Link Status (LINK) Indicates the modules current state with respect to
transmitting data on the EtherNet/IP network.
Off One of these conditions exists:
The module is not powered.
Verify there is chassis power.
Verify that the module is completely
inserted into the chassis and backplane.
Make sure the module has been
configured.
No link exists on the port.
Flashing green Activity exists on the port.
Green Activity exists on the port.
3 OK Status (OK) Indicates the modules current state. For example,
this status indicator indicates if the module is
executing power-up testing, in the process of a
firmware update or operating normally.
Off The module is not powered.
Verify there is chassis power.
Verify that the module is completely inserted
into the chassis and backplane.
Flashing green The module is not configured. The Module Status
display scrolls: BOOTP or
DHCP<Mac_address_of_module>
For example: BOOTP 00:0b:db:14:55:35
Configure the module.
Green The module is operating correctly. The Module
Status display scrolls: OK
<IP_address_of_this_module>
For example: OK 10.88.60.160