User Manual

Rockwell Automation Publication ENET-IN002F-EN-P - January 2014 23
Install a 1756 EtherNet/IP Communication Module Chapter 1
In the IP Address field, type the IP address.
In the Network Mask field, type the network mask address.
In the Gateway Address field, type the gateway address.
In the Primary Name Server field, type the IP address.
In the Secondary Name Server field, type the IP address.
In the Domain Name field, type the domain name.
In the Host Name field, type the host name.
7. Configure the port settings.
8. Click OK.
To Then
Use the default port speed and
duplex settings
Leave Auto-negotiate port speed and duplex checked.
This setting determines the actual speed and duplex setting.
Manually configure your ports
speed and duplex settings
Follow these steps.
1. Clear the Auto-negotiate port speed and duplex checkbox.
2. From the Current Port Speed pull-down menu, choose a port
speed.
3. From the Current Duplex pull-down menu, choose the appropriate
Duplex value, that is, Half Duplex or Full Duplex.
IMPORTANT
Consider the following when you configure the modules port settings:
If the module is connected to an unmanaged switch, leave Auto-
negotiate port speed and duplex checked or communication may
be impaired.
If you are forcing the port speed and duplex with a managed
switch, the corresponding port of the managed switch must be
forced to the same settings or the module will fail.