User Manual Owner's manual
Publication 1756-UM051B-EN-P - November 2000
Rack Optimized I/O 5-9
2. The Select Module Type window will open.
3. Select the 1756-IB16I digital input module from the list and click
on OK.
The Module Properties window will open.
4. Enter the following parameters (the values we used are listed in the
table):
Name Remote_Digital_Input
Slot 1
Comm Format Rack Optimization
Electronic Keying
(1)
(1)
See Appendix F for important information about Electronic Keying.
Compatible Module