General Specifications - 1756-EN2TXT
Attribute Value
Module location Any slot in the ControlLogix-XT chassis
Backplane current (mA) at
5V.1V DC
1 A
Backplane current (mA) at
24V DC
3 mA
Enclosure Type Rating None (open-style)
Isolation voltage 30 V (continuous), Basic Insulation Type
No isolation between USB and system.
Type tested at 853V AC for 60 s, Ethernet to system.
Power consumption 17.1 BTU/hr
Power dissipation 5.1 W
Wire size Ethernet connections:
RJ45 connector according to IEC 60603-7, 2 or 4 pair
Category 5e minimum cable according to TIA 568-B.1 or
Category 5 cable according to ISO/IEC 24702.
Wiring category
2 - on communications ports
(1)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1
.
North American temp code T4A
IEC temp code T4
Recommended USB cable
for USB port
Samtec cable, PN RSP-119350
USB port USB 1.1
USB device