User guide

ControlLogix-XT EtherNet/IP Bridge Module 19
Publication
1756-IN635A-EN-P - March 2009
OK Status Indicator
State Description
Off Verify that the module has 24V DC chassis power and that
the module is completely inserted into chassis and
backplane.
Flashing green The module is not configured.
Green The module is operating correctly.
Flashing red The module detected a recoverable fault. A configuration
error may have caused the fault. Check the module
configuration. If necessary, reconfigure the module.
Red The module detected an unrecoverable fault. Cycle power
to the module. If this does not clear the fault, replace the
module.
Red and alphanumeric
display scrolls 'Image
Update Needed'
Update the firmware image. Once the image is updated,
cycle power. If this does not clear the fault, replace the
module.
Flashing red and green The module is performing a power-up self-test.