Owner manual
ControlLogix-XT Data Highway Plus-Remote I/O Interface Module 25
Publication
1756-IN638A-EN-P - March 2009
Channel A and B Indicators
State Channel Mode Description Recommended Actions
Off All Not on line. Place channel on line.
Green RIO scanner Active RIO link. All
adap
ter modules are
present and not
faulted.
None - this is normal
opera
tion.
DH+ Operating. None - this is normal
opera
tion.
Green
f
lashing
RIO scanner One or more nodes
faulted or failed.
Check power at other racks.
DH+ No other node on the
network.
Check cables.
Red All Hardware fault. Reboot module. If red
reoccurs, rep
lace module.
Red
f
lashing
RIO scanner Faulted adapters
detected.
• Check cables.
• Check power at other
chassis.
DH+ Duplicate node
detected
.
Check node address.