Instruction Manual

Rockwell Automation Publication 1756-UM514C-EN-P - June 2014 17
About the Module Chapter 1
Configure Switches
Before installing the module, you must set the network type switches for DH+ or
RIO, depending on your application. For a channel configured as DH+, you
must also select a node address within the range of 00-77. Node addresses are set
and displayed in octal.
Set the network type and node address switches as shown in the Figure.
IMPORTANT
If your module uses the 230k DH+ network (that is Channel A switch set to
3), Channel B is disabled.
Also, node address switches do not apply if you are using remote I/O.