Configure Your 1756-DHRIO Module
After installing your 1756-DHRIO module, you must configure it. For more
information, refer to the
Data Highway Plus-Remote I/O Communication
Interface Module User Manual, publication 1756-UM514.
If the channel
A or B
indicator is
in this
channel mode
then the channel
status is
take this action
Off All Not on line. Place channel on line.
Green RIO scanner Active RIO link. All
adapter modules are
present and not
faulted.
None, normal operation.
DH+ Operating. None, normal operation.
Green
flashing
RIO scanner One or more nodes
faulted or failed.
Check power at other
racks.
DH+ No other node on the
network.
Check cables.
Red All Hardware fault. Reboot module. If red
reoccurs, replace module.
Red flashing RIO scanner Faulted adapters
detected.
Check cables.
Check power at other
racks.
DH+ Duplicate node
detected.