User Manual
Table Of Contents
- 1756-UM532A-EN-P
- Important User Information
- Table of Contents
- Purpose of This Manual
- Preface
- 1756-DH485 Module Overview
- Overview of the DH-485 Network
- Introduction
- DH-485 Network Description
- DH-485 Network Protocol
- DH-485 Token Rotation
- DH-485 Network Initialization
- Devices that Use the DH-485 Network
- 1747-AIC Isolated Link Coupler for DH-485
- 1761-NET-AIC Advanced Interface Converter Product Overview
- Operating Modes
- Device Compatibility
- Misconception about the 1761-NET-AIC Converter
- 1747-UIC USB to DH-485 Interface Converter
- Example System Configuration
- Important Planning Considerations
- Additional Resources
- Use Data Highway 485 Network
- Use RSLinx Software to Create a Routing Table
- Communicate from an SLC 5/03 Controller to a Logix Controller over a DH-485 Network
- Communicate Between SLC Controllers over DH+ and DH485 Networks
- Communicate Between a PLC-5 Controller and a Remote SLC 5/03 Controller over Multiple DH-485 Networks
- Communicate from an SLC 5/05 Controller to an SLC 5/03 Controller over an EtherNet/IP Network
- Communicate to a SLC 5/03 Controller on a DH-485 Network
- Communicate from a Logix Controller to an SLC 5/03 Controller over EtherNet/IP and DH-485 Networks
- Specifications
- Troubleshoot the 1756-DH485 Module
- Index
- How Are We Doing?
- Rockwell Automation Support
- Backcover

1 Publication 1756-UM532A-EN-P - May 2006
Chapter
4
Use RSLinx Software to Create a Routing
Table
Introduction
This chapter describes how to configure your 1756-DH485 module in
DH-485 applications. For more information on the configuration software,
refer to the online help in each.
Choose the Correct
Software
The programming software you need is dependent on what products you are
using with the 1756-DH485 module. The table below explains what software is
needed for your application.
For See
Choose the Correct Software 4-1
Use RSLinx Software to Create a Routing
Table
4-2
Create the Routing Table 4-3
Software Needed for 1756-DH485 Applications
If you are using this product with the
1756-DH485 module to read/write data
in a DH-485 application
You must use this software
SLC Controllers RSLinx, version 2.43 or later
RSLogix 500, version 6.3 or later
ControlLogix Controllers RSLinx, version 2.43 or later
RSLogix 5000