Installation Instructions User Manual
28 ControlLogix ControlNet Interface Module
Publication
1756-IN604A-EN-P - February 2006
ControlNet Network Channel Status Indicators
The ControlNet network channel status indicators appear in one of the
following states:
• Steady - indicator is on continuously in the defined state.
• Alternating - the two indicators alternate between the two defined
states at the same time (applies to both indicators viewed together).
The two indicators are always in opposite states, out of phase.
• Flashing - the indicator alternates between the two defined states
(applies to each indicator viewed independent of the other). If both
indicators are flashing, they must flash together, in phase.
The ControlNet Network Channel Status Indicators table summarizes the
meanings of these states.
ControlNet Network Channel Status Indicators
Cause Action
Off No power None or power up.
Steady red Faulted unit Cycle power or reset unit.
If fault persists, contact A-B
representative or distributor.
Alternating
red/green
Self-test None
Alternating red/off Incorrect node configuration Check network address and other
ControlNet network configuration
parameters.
Cause Action
Off Channel disabled Program network for redundant
media, if required.
Steady green Normal operation None
Flashing green/off Temporary errors None; unit will self-correct.
and
AB
or
AB