Installation Instructions Owner manual
30 ControlLogix-XT ControlNet Interface Module
Publication
1756-IN634A-EN-P - April 2009
ControlNet Indicator States (A AND B)
State Cause Action
Off There is no power. No action is required, or apply
power
.
Steady red Unit has faulted. Cycle power or reset unit.
If fault persists, contact a
Rock
well Automation
representative or distributor.
Alternating
re
d/green
A self-test is being conducted. No action is required.
Alternating
re
d/off
Node has been configured
incorrectly.
Check network address and other
ControlNet configuration
parame
ters.
ControlNet Channel Troubleshooting (A OR B)
State Cause Action
Off Channel has been disabled. Program network for redundant media,
if required.
Steady green This is normal operation. No action is required.
Flashing
g
reen/off
Temporary errors exist. None; unit will self-correct.
Node is not configured to go
on
line.
Make sure the configuration manager
node (keeper) is present and working,
and the selected address is not
greater than the maximum
unscheduled node address (UMAX).
(1)
(1)
The configuration manager node (keeper) is the node responsible for distributing ControlNet
configuration data to all nodes on the network.
Flashing red/off A media fault exists. Check media for broken cables, loose
connectors, or missing terminators.
No other nodes are present
on
the network.
Add other nodes to the network.