Installation Instructions Owner manual

26 ControlLogix-XT ControlNet Interface Module
Publication
1756-IN634A-EN-P - April 2009
Solid
green
OK This is normal operation. There is at least one
connection to or through the
module. No action is required.
INIT Module is initializing. No action is required.
PASS This message is displayed
momentarily
upon completion
of a successful power-up test.
No action is required.
CMPT
(1)
The secondary module is
compatible with its partner.
No action is required.
DSNP
(1)
The secondary module is
disqualified with no partner.
Check the corresponding slot
of the primary chassis for the
module type and revision.
PwDS
(1)
The module is primary with a
disqualified secondary
partner.
Check the type and revision of
the
1756-CN2RXT module.
PQgS
(1)
The module is primary with a
qualifying secondary partner.
Redundant system status. No
action is required.
PwQS
(1)
The module is primary with a
qualified secondary partner.
PwNS
(1)
The module is primary with no
secondary partner.
Check corresponding slot of
secondary chassis for correct
module.
QgS
(1)
The secondary module is
qualifying.
Redundant system status. No
action is required.
QS
(1)
The secondary module is
qualified.
A#XX This message is the node
addre
ss where XX is an
address from 01...99.
No action is required.
MACID
SW
ITCH
ERROR
Node address switch changed
after you cy
cled power.
No action is required, but we
recommend that you either
return switches to their
original settings or replace the
module, since this could
indicate a latent hardware
anomaly.
OK
In
dicator
Display Cause Recommended Action