Installation Instructions Owner manual
ControlLogix-XT ControlNet Interface Module 25
Publication
1756-IN634A-EN-P - April 2009
Flashing
red
Image
update
Needed
Boot image running.
Main firmware image needs
to be update
d.
Update the module’s firmware
by
using the ControlFlash
utility.
DUPLICATE
NODE
DETECTED
The module’s network address
is the same as
another
module’s on the link.
1. Remove power from the
chassis.
2. Remove the module from
the chassis.
3. Set the switches to their
final value. See page 11
.
4. Replace the module in the
chassis.
5. Apply power to the chassis.
Flash in
progress
Flash update is in progress. No action is required.
If communication to the
module is lost during a F
lash
Update, this message will
continue to be displayed even
though the module will not be
able to finish the update.
You must remove power from
the
module to recover, and
then flash again.
TEST Module is executing a
power
-up test.
No action is required.
If the display persists for more
tha
n 45 seconds, replace the
module because it has failed.
OK
In
dicator
Display Cause Recommended Action