Installation Instructions Owner manual

24 ControlLogix-XT ControlNet Interface Module
Publication
1756-IN634A-EN-P - April 2009
Red Reset
Complete-
Change
Sw
itch
Settings
Module’s network address is
s
et to 00, an invalid
ControlNet address.
1. Remove power from the
chassis.
2. Remove the module from
the chassis.
3. Set the switches to their
final value. See page
page 11
.
4. Replace the module in the
chassis.
5. Apply power to the chassis.
FAIL This code is displayed when
the power-up test fails.
Replace the module.
Backplane
Ini
t
(1)
The module is waiting for the
redundant module to complete
power up.
None required.
Stop Service
Rec
eived
A non-redundant module is
placed into a redundant
secondary chassis. The
module was commanded to
stop functioning by the
redundancy module
(RM/SRM).
1. Remove the non-redundant
modu
le from the redundant
secondary chassis
2. Replace the non-redundant
module with the redundant
module.
This could occur if a
1756
-CN2RXT module running
Boot code is inserted into a
chassis along with a
1756-SRM or 1756-RM
module.
For redundant control, the
1756
-CN2RXT module is to be
used with a 1756-RM module.
It should not be used with a
1756-SRM module.
1. Insert the module into a
chassis
that does not
contain a 1756-SRM or
1756-RM module.
2. Update the module’s
firmware using ControlFlash
software.
OK
Indicator
Display Cause Recommended Action