Instruction Manual
111Rockwell Automation Publication 1756-UM010B-EN-P - December 2011
Configuring the Configurable Flowmeter Module 111
C.Operations[0].kFactStruct.FreqAtKFactor[5] Float REAL Freq[5] for KFactor [5] 0.0
C.Operations[0].kFactStruct.FreqAtKFactor[6] Float REAL Freq[6] for KFactor [6] 0.0
C.Operations[0].kFactStruct.FreqAtKFactor[7] Float REAL Freq[7] for KFactor [7] 0.0
C.Operations[0].kFactStruct.FreqAtKFactor[8] Float REAL Freq[8] for KFactor [8] 0.0
C.Operations[0].kFactStruct.FreqAtKFactor[9] Float REAL Freq[9] for KFactor [9] 0.0
C.Operations[0].kFactStruct.FreqAtKFactor[10] Float REAL Freq[10] for KFactor [10] 0.0
C.Operations[0].kFactStruct.FreqAtKFactor[11] Float REAL Freq[11] for KFactor [11] 0.0
C.Operations[0].kFactStruct.FreqAtKFactor[12] Float REAL Freq[12] for KFactor [12] 0.0
C.OutputSetup[0].FaultMode Decimal SINT Sets the state of output 0 when
communications are lost with the
owner-controller in Fault Mode
0 = Continue operation
1 = Reset Output 0 to OFF when in Fault Mode
2 = Set Output 0 to ON when in Fault Mode
1
C.OutputSetup[0].ProgMode Decimal SINT Sets the state of output 0 when
communications are lost with the
owner-controller in Program Mode
0 = Continue operation
1 = Reset Output 0 to OFF when in Program
Mode
2 = Set Output 0 to ON when in Program
Mode
0
C.OutputSetup[0].DynamicError Decimal SINT Sets the state of output 0 when a dynamic
error occurs
0 = Continue operation
1 = Reset Output 0 to OFF on Error
2 = Set Output 0 to ON on Error
0
C.OutputSetup[0].TriggerOn Decimal SINT Sets when output 0 energizes
0 = No Action
1 = Frequency
2 = Acceleration
3 = Full Flow State
4 = Trickle Flow State
5 = Prover Run State (N/A in this mode)
6 = Prover Range State (N/A in this mode)
0
C.OutputSetup[0].TieToCounter Ties a channel to output 0
0 = No connection
1 = Connect Channel0 to Output0
2 = Connect Channel1 to Ouput0
0
C.Operations[0].OperationalMode Decimal SINT Sets the module’s operational mode.
0 = OFF
1 = Totalizer Mode
2 = Non-Resettable Totalizer Mode
3 = High Resolution Frequency Mode
1
Table 9 - Tag Changes Required for Totalizer Mode Using Filler Function
Name Style Data type Definition Enter
this
Value