Instruction Manual

90 Publication 1753-UM001C-EN-P - March 2010
Chapter 8 Wire and Configure the 1753-IB16XOB8 Module
Terminal Connections
See the wire size and terminal torques specifications on page 290.
Digital outputs are connected to these terminals.
Terminal
Number
Designation Function
1 S+ Reference pole for negative-switching digital outputs
2 S+ Reference pole for negative-switching digital outputs
3 S+ Reference pole for negative-switching digital outputs
4 S+ Reference pole for negative-switching digital outputs
5 S- Reference pole for positive-switching digital outputs
6 S- Reference pole for positive-switching digital outputs
7 S- Reference pole for positive-switching digital outputs
8 S- Reference pole for positive-switching digital outputs
9 1- Digital output 1, negative-switching
10 1+ Digital output 1, positive-switching
11 2- Digital output 2, negative-switching
12 2+ Digital output 2, positive-switching
13 3- Digital output 3, negative-switching
14 3+ Digital output 3, positive-switching
15 4- Digital output 4, negative-switching
16 4+ Digital output 4, positive-switching
17 5- Digital output 5, negative-switching
18 5+ Digital output 5, positive-switching
19 6- Digital output 6, negative-switching
20 6+ Digital output 6, positive-switching
21 7- Digital output 7, negative-switching
22 7+ Digital output 7, positive-switching
23 8- Digital output 8, negative-switching
24 8+ Digital output 8, positive-switching
123456 87
S+
DO DO
S+ S+ S+ S- S- S- S-
91011121314 1615
1- 1+ 2- 2+ 3- 3+ 4+4- 5- 5+ 6- 6+ 7- 7+ 8+8-
17 18 19 20 21 22 2423