Instruction Manual
Publication 1753-UM001C-EN-P - March 2010 73
Wire 1753-IB16, 1753-OB16, and 1753-IB20XOB8 Modules Chapter 6
Wire the 1753-OB16 Output
Module
Operating Voltage Considerations
The 1753-OB16 output module has a total current capacity (16 A)
higher than the terminal block current limitation (10 A). Therefore, it
features two separate operating voltage supply connections if more
than 10 A is used by the module. The two output groups are shown
below. Each group has a current capacity of 8 A.
Safety-related Digital Outputs
The module has 16 digital outputs (DO1 to DO16) whose status is
indicated via status indicators.
Each output is rated for up to 1 A at 60 °C (140 °F) or 2 A at
40 °C (104 °F). However, each group of 8 outputs may not exceed 8 A
total. For heat dissipation, intersperse high-current and low-current
outputs so that all the high-current outputs are not next to each other.
Group Outputs
1 1, 2, 3, 4, and 9, 10, 11,12
2 5, 6, 7, 8 and 13, 14, 15, 16
L-L- L+ L+
1L- L-DO1 2 3 4
123456
123456
5L- L-DO2 6 7 8
789101112
789101112
9L- L-DO1 10 11 12
13 14 15 16 17 18
13 14 15 16 17 18
13L- L-DO2 14 15 16
19 20 21 22 23 24
19 20 21 22 23 24
24V DC
L-L- L+ L+
24V DC
RUN
24 V DC
PROG
ERROR
FAULT
FORCE
BL
OSL
GuardPLC Ethernet
10/100 BaseT
1
(—)
2
(—)
1753-OB16
16 DC Outputs
Group 2Group 1
1LS+ LS+
LS+
LS+
L-
DO1
234
123456
5L-
DO2
678
789101112
9L-
DO1
10 11 12
13 14 15 16 17 18
13 L-
DO2
14 15 16
19 20 21 22 23 24
123456 789101112
13 14 15 16 17 18