Instruction Manual

Publication 1753-UM001C-EN-P - March 2010 295
Specifications Appendix A
Shock, operating 15 g
Relative humidity 10 … 95% noncondensing
Emissions Group 1, Class A
ESD immunity 6 kV contact discharges
8 kV air discharges
Radiated RF immunity 10V/m with 1kHz sine-wave 80% AM from 80 MHz…2000 MHz
EFT/B immunity ±2 kV @ 5 kHz on power ports
±1 kV @ 5 kHz on signal ports
±1 kV @ 5 kHz on communication ports
Surge transient
immunity
±500V line-line (DM) and ±500V line-earth (CM) on DC power
ports
±1 kV line-earth (CM) on signal ports
±1 kV line-earth (CM) on communication ports
Conducted RF
immunity
10Vrms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Enclosure type rating meets IP20
Mechanical Dimensions
Width 207 mm (8.14 in.) including housing screws
Height 114 mm (4.49 in.) including latch
Depth 86 mm (3.38 in.) including grounding bolt
Weight 1.3 kg (3.47 lb)
Certifications
(when product is marked)
c-UL-us UL Listed Industrial Control Equipment, certified for US and
Canada
CE European Union 89/336/EEC EMC Directive, compliant with:
EN 61000-6.2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
European Union 73/23/EEC LVDDirective, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Australian Radiocommunication Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Functional Safety Certified by TÜV
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
.