Chapter 19 Use GuardPLC Controller as an Adapter
3. Double-click the object to open the Properties dialog box.
4. Enter the desired Field Width and Decimal Point display
information.
5. Enter a name for the Read Tag.
6. Click the Edit Tag button to open the Tag Form dialog box.
7. Configure the tag as shown below.
Parameter Setting
Messaging Type CIP
Node Name Enter the name of the GuardPLC controller that will receive the command.
Service Code Choose Get Attribute Single to indicate that this is a read operation.
Class Code Enter 4, for an assembly object.
Instance Number Enter 121 to indicate the GuardPLC target input assembly that was created for the
PanelView Standard terminal to read from.
Attribute Enter 3 to provide access to the assembly object instance data.
Byte Offset Index into the GuardPLC output assembly x number of bytes, then read the data.