Instruction Manual

128 Publication 1753-UM001C-EN-P - March 2010
Chapter 14 Use the Control Panel to Monitor Status
Distributed I/O Tab
HH (High-level High-speed)
State Tab
This field Displays
Resource The name of the module.
System.Rack The System.Rack ID of the module.
State The status of the I/O module:
Run
Stop/Valid_Configuration
Stop/Invalid_Configuration
Error_Stop
not connected
This field Displays
Bus Cycle Time The time in milliseconds for a Token cycle. The value is 0, if Token Passing is off (any Cleanroom profile).
Resource The name of the controller.
LinkID The controller network ID.
State The status of communication.
RspT If Link Mode is TCS direct (Token Passing OFF), RspT is the ResponseTime of the HH profile for a message
from PES
1
PES
2
PES
1
, based on the network hardware and topology. This parameter cannot be
changed by the user.
If Link Mode is TCS TOKCYC (Token Passing ON), RspT is part of the Bus Cycle Time.
Link Mode TCS direct when Token Passing is OFF.
TCS TOKCYC when Token Passing is ON.
Token Group ID The ID of the Token Group.