Instruction Manual

GuardPLC 1800 Controllers 13
Rockwell Automation Publication 1753-IN002C-EN-P - June 2010
Digital Output Terminals
Terminals accommodate wires up to 1.5 mm
2
(16 AWG). See the terminal torque specifications
on page 21. Digital outputs are connected to these terminals.
For connection of a load, the reference pole L- of the concerned channel group must be used
(2-pole connection). Although L- at terminals 1 and 6, 7 and 12 is connected internally to L- on
he power supply input, it is strictly recommended to use 1 and 6 for outputs 1…4 only and 7 and
12 for outputs 5…8 only. EMC testing was performed in this manner.
Terminal Number Designation Function Current
1 L- Reference pole
2 1 Digital output 1 0.5 A
3 2 Digital output 2 0.5 A
4 3 Digital output 3 0.5 A
5 4 Digital output 4 (for increased load) 2.0 A
6 5 Digital output 5 0.5 A
7 6 Digital output 6 0.5 A
8 7 Digital output 7 0.5 A
9 8 Digital output 8 (for increased load) 2.0 A
10 L- Reference pole
123456
1234
1L- L-DO 2
(2A)(2A)
345 678
56
78910
10789