Installation Instructions GuardPLC 1800 Controllers Catalog Numbers 1753-L32BBBM-8A, 1753-L32BBBP-8A Topic Page Important User Information 2 About the Controller 3 General Safety 3 Install the Controller 4 Mount the Controller 5 Ground the Controller 5 Wire the Controller 6 Make Communication Connections 15 Reset Push Button 17 Controller Tests 18 Status Indicators 19 Specifications 20 Additional Resources 24
GuardPLC 1800 Controllers Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices.
GuardPLC 1800 Controllers 3 About the Controller The GuardPLC 1800 controller is a programmable electronic system featuring 24 digital inputs, 8 digital outputs, 2 counters, 8 analog inputs, and 4 connections for GuardPLC Ethernet communication.
GuardPLC 1800 Controllers Environment and Enclosure ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11.
GuardPLC 1800 Controllers 5 Mount the Controller IMPORTANT For effective cooling, mount the controller following these guidelines • • • • Mount the controller horizontally. Provide a gap of at least 100 mm (3.94 in.) above and below the controller. Select a location where air flows freely or use an additional fan. Do not mount the controller over a heating device. The controller cannot be panel-mounted. Mount the controller to a DIN rail by following these steps. 1.
GuardPLC 1800 Controllers Wire the Controller The following section describe how to connect the voltage supply and wire the controller’s digital inputs and outputs. Connect the Voltage Supply The 24V DC voltage supply must feature galvanic isolation (in accordance with EN 60950 or UL 1950) since inputs and outputs are not electrically isolated from the processor.
GuardPLC 1800 Controllers 7 Safety-Related Digital Inputs The controller has 24 digital inputs whose status is indicated via status indicators when the controller is in RUN mode. LS+ is a voltage source that provides 24V DC for a group of eight dry contact inputs. There are three groups on the GuardPLC 1800 controller.
GuardPLC 1800 Controllers The safe state of an input is indicated by a 0 signal being passed to the user program logic. If the test routines detect a fault in the digital inputs, a 0 signal is processed in the user program for the defective channel. When a fault occurs, the inputs are switched off (0). Follow the closed-circuit principle for external wiring when connecting sensors. To create a safe state in the event of a fault, the input signals revert to the de-energized state (0).
GuardPLC 1800 Controllers Terminal Number Designation Function 31 LS+ Sensor supply for inputs 17…24 32 17 Digital input 17 33 18 Digital input 18 34 19 Digital input 19 35 20 Digital input 20 36 21 Digital input 21 37 22 Digital input 22 38 23 Digital input 23 39 24 Digital input 24 40 L- Reference pole 9 LS+, not L+, should be used for short-circuit protection.
GuardPLC 1800 Controllers Analog Input Terminals External Power Supply + - + - Single-ended current + - Single-ended voltage External Power Supply GuardPLC 1800 controller with a 4-wire device + - 10kΩ 500Ω AI AI T1 I1 L- T2 I2 LT3 I3 L- T4 I4 L- 41 42 43 44 45 46 47 48 49 50 51 52 AI AI T5 I4 L- T6 I6 L- AI T7 I7 L- T8 I8 L- 53 54 55 56 57 58 59 60 61 62 63 64 AI T1 I1 L- T2 I2 L- 41 42 43 44 45 46 T3 I3 AI L- T4 I4 L- 47 48 49 50 51 52 T5 I4 AI L- T6 I6 L- 53 54 55 56 57
GuardPLC 1800 Controllers 11 GuardPLC 1800 with a 2-wire Device AI AI T1 I1 L- T2 I2 L- 41 42 43 44 45 46 T3 I3 AI L- T4 I4 L- 47 48 49 50 51 52 AI T5 I4 L- T6 I6 L- 53 54 55 56 57 58 T7 I7 L- T8 I8 L- 59 60 61 62 63 64 - - + + 24V DC + Power Supply COM 2-wire Device with Power Source from GuardPLC controller 2-wire Device with External Power Source Terminals accommodate wires up to 1.5 mm2 (16 AWG). The analog inputs are connected to these terminals.
GuardPLC 1800 Controllers Terminal Number Designation 59 T7 Function Transmitter supply 7 60 I7 Analog input 7 61 L- Reference pole 62 T8 Transmitter supply 8 63 I8 Analog input 8 64 L- Reference pole Connecting the I/O Circuits The I/O circuits are connected to the front plate of the controller using pluggable terminals. For controls with analog inputs, shielded cabling is fed in from below so that the shielding can be connected to the shield contact plate using a clip.
GuardPLC 1800 Controllers 13 Digital Output Terminals DO 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 L- 1 2 3 4 5 (2A) 6 7 8 L(2A) Terminals accommodate wires up to 1.5 mm2 (16 AWG). See the terminal torque specifications on page 21. Digital outputs are connected to these terminals. Terminal Number Designation Function 1 L- Reference pole Current — 2 1 Digital output 1 0.5 A 3 2 Digital output 2 0.5 A 4 3 Digital output 3 0.
GuardPLC 1800 Controllers TIP L- DO 8 … DO 7 DO 2 L- DO 1 Example: Connecting Actuators to the Outputs Inductive loads can be connected without a protection diode on the load. However, Rockwell Automation strongly recommends that a protection diode be fitted directly to the load to suppress any interference voltage. A 1N4004 diode is recommended. High-speed Counter Connections The controller features two independent high-speed counters.
GuardPLC 1800 Controllers 15 High-speed Counter Terminals HSC A1 B1 Z1 L- A2 B2 Z2 65 69 66 67 68 70 L- 71 72 Terminals accommodate wires up to 1.5 mm2 (16 AWG). Counters are connected to these terminals.
GuardPLC 1800 Controllers OPC Server The GuardPLC 1800 controller is an OPC client. An OPC server, catalog number 1753-OPC, is available from Rockwell Automation and lets computer applications read and write data to and from the GuardPLC controller. MAC Address The media access control (MAC) address of the controller can be found on the label positioned over both lower RJ45 connections.
GuardPLC 1800 Controllers 17 Reset Push Button The controller is equipped with a reset push button. Reset via the push button is necessary under the following conditions. • You forget the password to go online via the programming software. • You are unable to determine the IP address and SRS of the controller. The push button is accessible through a small round hole at the top of the housing, approximately 4…5 cm (1.6…2.0 in.) from the left rim and recessed approximately 9.5 mm (0.375 in.).
GuardPLC 1800 Controllers Controller Tests In addition to the tests for safety, the controller tests the supply voltage and controller temperature. Supply Voltage Tests The supply voltage (24V DC) is monitored and the alarm and system shutdown are controlled according to the voltage levels listed below. Voltage Level System Condition 19.3 to 28.8V Normal < 19.3V Alarm state 1 (internal variables are written) < 15.4V Alarm state 2 (prepares for shutdown) < 13.
GuardPLC 1800 Controllers 19 Status Indicators Indicator State 24V DC On 24V DC operating voltage present. Off No operating voltage. On This is the normal status of the controller. A routine, which has been loaded into the controller, is executed. The controller processes input and output signals, carries out communication, and performs hardware and software tests. Flashing The controller is in STOP mode and is not executing a routine. All system outputs are reset.
GuardPLC 1800 Controllers Communication via GuardPLC Ethernet is indicated by two small status indicators integrated into all connecting sockets. Indicator State Description Green On Full-duplex operation Flashing Collision Yellow Off Half-duplex operation, no collision On Connection established Flashing Interface activity Additional nonsafety-related communication occurs on the field buses and is indicated by the status indicators.
GuardPLC 1800 Controllers 21 Technical Specifications – GuardPLC 1800 Controllers Wire type Shielded on Ethernet, analog, and high-speed counter inputs Terminal block torque 0.51 N•m (4.5 lb•in) Fuse (external) 24V DC power: 10 A (time-lag) Enclosure type rating Meets IP20 Width, approx. 257 mm (10.1 in.) including housing screws Height, approx. 114 mm (4.49 in.) including latch Depth, approx. 66 mm (2.60 in.) including grounding bolt Weight, approx. 1.2 kg (2.
GuardPLC 1800 Controllers Technical Specifications – GuardPLC 1800 Controllers Counters Number of counters 2 (not electrically isolated) Inputs 3 per counter (A, B, Z) Input voltages 5V and 24V DC High signal (5V DC): 4…6V High signal (24V DC): 13…33V Low signal (5V DC): 0…0.5V Low signal (24V DC): -3…5V Input currents 1.4 mA @ 5V DC 6.5 mA @ 24V DC Input impedance 3.
GuardPLC 1800 Controllers 23 Environmental Specifications – GuardPLC 1800 Controllers Attribute 1753-L28BBB-M, 1753-L28BBB-P Temperature, nonoperating -40…85 °C (-40…185 °F) • IEC 60068-2-1 (Test Ab, Unpackaged nonoperating cold) • IEC 60068-2-2 (Test Bb, Unpackaged nonoperating dry heat) • IEC 60068-2-14 (Test Na, Unpackaged nonoperating thermal shock) Temperature, operating 0…60 °C (32…140 °F) • IEC 60068-2-1 (Test Ad, operating cold) • IEC 60068-2-2 (Test Bd, operating dry heat) • IEC 60068-2-14
Certifications Certification (when product is marked)(1) 1753-L28BBBM-8A, 1753-L28BBBP-8A c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CE European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1 Meas./Control/Lab., Industrial Requirements • EN 61000-6.