Safety Scanner for GuardPLC Controllers User Manual
Publication 1753-UM002A-EN-P - July 2005
10-8 Monitor Status
0001 0x080D The target’s unique node identifier was not set.
0001 0x080E The target’s unique node identifier does not match. The
message was likely routed to this node in error.
0001 0x080F The configuration operation was not allowed.
0004
0005
0000 Extended status is out of memory.
0004
0005
0001 Extended status is out of instances.
000F 0203 The connection has timed out.
00FF 2001 One or more of the system address segments that a device
must interpret to direct a message to its destination object is
excessive.
00FF 2002 A parameter value is bad.
00FF 2018 Semaphore reject occurred.
00FF 201B Size is too small.
00FF 201C Size is invalid.
00FF 2100 Privilege failure occurred.
00FF 2102 Password is invalid.
00FF 2103 No password was issued.
00FF 2104 The address is out of range.
00FF 2106 Data is in use.
00FF 2107 Type is invalid and not supported.
00FF 2108 The controller is in the upload and download mode.
00FF 2109 An attempt was made to change the number of array
dimensions.
00FF 210A The symbol name is invalid.
00FF 210B The symbol does not exist.
00FF 210E The search failed.
00FF 210F The task cannot start.
00FF 2110 Unable to write.
00FF 2111 Unable to read.
00FF 2112 The shared routine is not editable.
00FF 2113 The controller is in fault mode.
00FF 2114 Run mode is inhibited.
General
Status
Error Code
(00gg)
Extended
Error Code
(nnnn)
Description