Safety Scanner for GuardPLC Controllers User Manual

Publication 1753-UM002A-EN-P - July 2005
Monitor Status 10-7
Safety Connection Extended Error Codes
General
Status
Error Code
(00gg)
Extended
Error Code
(nnnn)
Description
0001 0100 The connection is in use.
0001 0103 Transport is not supported.
0001 0106 Ownership conflict occurred.
0001 0107 The connection was not found.
0001 0108 Connection type is invalid.
0001 0109 Connection size is invalid.
0001 0110 The module is not configured.
0001 0111 Expected Packet Rate value is not supported.
0001 0114 This is the wrong module.
0001 0115 Device type is incorrect.
0001 0116 Module revision is incorrect.
0001 0118 The configuration format is invalid.
0001 011A The application is out of connections.
0001 0203 The connection has timed out.
0001 0204 An unconnected message has timed out.
0001 0205 Unconnected send parameter error occurred.
0001 0206 The message is too large.
0001 0301 There is no buffer memory.
0001 0302 Bandwidth is not available.
0001 0303 Dynamic I/O resources are not sufficient.
0001 0305 Signatures match.
0001 0311 The port is not available.
0001 0312 A link address is not available.
0001 0x0315 Safety Connection Type name is invalid (not equal to 0x50).
0001 0317 The connection is not scheduled.
0001 0x0801 The RPI is not compatible with previously established
multicast connections. All multi-cast consumers must
request the same RPI.
0001 0x0802 Safety connection size is invalid.
0001 0x0803 Safety connection format is invalid.
0001 0x0805 Ping interval EPI multiplier was out of range (10 to 10000).
0001 0x0806 Time Coordination Message Minimum Multiplier was out of
range (10 to 10000).
0001 0x0807 Time Expectation Multiplier was out of range (0 to 42969).
0001 0x080A CPCRC value in Safety Open and calculated CPCRC value.
0001 0x080B Time Correction Connection ID is invalid.
0001 0x080C Configuration Signatures do not match. The Configuration
Signature was non-zero and did not match the value in the
target.