Safety Scanner for GuardPLC Controllers User Manual

Publication 1753-UM002A-EN-P - July 2005
Install the 1753-DNSI 2-7
Connect to the DeviceNet Network
Attach the connector to the module’s DeviceNet port. Tighten the
screws on the connector to 0.6 to 0.7 Nm (5 to 6 in-lb).
High-speed Safety Protocol (HSP) Connections
The module ships with the cable used to connect its HSP port to the
GuardPLC controller’s COMM3 (ASCII/HSP) port. The minimum bend
radius of the 1753-CBLDN is:
30 mm (1.18 in.) when the cable is permanently restrained by
the use of a wire tie, cable trough, or other means.
60 mm (2.36 in.) when unrestrained.
IMPORTANT
The maximum length of the cable connection
between the module and the GuardPLC controller is
0.75 m (2.46 ft). To achieve a SIL 3 rating, you must
use the 1753-CBLDN cable, which is shipped with
the module.