Safety Scanner for GuardPLC Controllers User Manual

Publication 1753-UM002A-EN-P - July 2005
Calculate Safety Connection Bandwidth D-3
3 to 250 Bytes
In the equation below:
A = 1 ÷ Data_RPI ÷ 0.001
B = (2 x Safety_Data_Size) + 8
C = (B ÷ 8) rounded to the nearest whole number
D = 1 ÷ (Data_RPI x 100) ÷ 0.001
E = (B x 8 x bit_stuffing_factor) rounded to the nearest whole number
%Bandwidth =
100 x
({A x [(57 x C) + (B x 8) + E] +
2 x (D x 115 x Number_of_Consumers)} ÷ Baud_Rate
)