Safety Scanner for GuardPLC Controllers User Manual

Publication 1753-UM002A-EN-P - July 2005
A-2 Specifications
Electrical/EMC
Emissions CISPR 11: Group 1, Class A
ESD Immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF Immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 30 MHz
to 2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 MHz 50% Pulse 100% AM at 1890
MHz
3V/m with 1 kHZ sine-wave 80% AM from 2000 MHz
to 2700 MHz
EFT/B immunity IEC 61000-4-4:
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on communications ports
Surge Transient
Immunity
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on
power ports
±2 kV line-earth (CM) on communications ports
Conducted RF Immunity IEC 61000-4-6:
10Vrms with 1 kHz sine-wave 80% AM from 150 kHz
to 80 MHz