Catalog Number
Explanation
The following chart describes the parts that make up the catalog number for a
DataSite configured panel.
Radio
Code Brand Frequency Comm.
NR None None None Space for radio included.
PS9E Prosoft 900 MHz Ethernet
PS9S Prosoft 900 MHz Serial
PS24E Prosoft 2.4 GHz Ethernet
PS24S Prosoft 2.4 GHz Serial
DL9E Datalinc 900 MHz Ethernet
DL9S Datalinc 900 MHz Serial
DL24E Datalinc 2.4 GHz Ethernet
DL24S Datalinc 2.4 GHz Serial
FW9E FreeWave 900 MHz Ethernet
FW9S FreeWave 900 Mhz Serial
FW24E FreeWave 2.4 GHz Ethernet
FW24S FreeWave 2.4 GHz Serial
Code Product Type
F Enclosed with Flow Measurements (AGA)
R Enclosed, RTU only
Code Enclosed Options
Blank No options
AL Aluminum NEMA 4X enclosure, 60.96 x 50.8 x 25.4 cm (24 x 20 x 10 in.).
See note 6.
TB RTU wired to control terminals. If not selected, no terminals provided.
HMI IDEC display unit HG1X-222. See note 5.
24V 24V system voltage. This means 24V is available for field devices, but the
DataSite panel, radio and batteries remain at 12V DC. See note 8.
1-4 5 6 7-8 9 10 11 12-13 14 15-18 19 20-21 22 23 24-25
1748 - F DC - P - 14 - PS9E - 10 Y - TB
Antenna Cable Length
Code Feet Meters
NC None None
10 10 3.1
25 25 7.6
50 50 15.2
100 100 30.5
Bulletin Number
1748 DataSite Enclosure in
UL Type 4X polycarbonate
Code Antenna Brand
Y Yagi
OOmni
NA No antenna
Code Analog Inputs
DC 0…10V DC
MA 4…20 mA
Code Mounting Type
W Wall mounting kit
P Pipe mounting kit
Notes:
1. Unit is UL Class I Division 2 certified only when FreeWave 900 MHz radios are selected (options FW9E and FW9S).
2. Solar panels are available from local RA authorized distributors.
Please see DataSite Configured Panel Application Techniques, publication 1748-AT001A-EN-P for proper sizing and selection.
Solar panels must meet UL Class I Division 2 if required.
3. Standard system voltage is 12V DC.
4. Radio surge suppressor included when a radio is specified.
5. Human-machine interface (HMI) option includes:
2-line, 16-character or 4-line, 20 character backlit LCD HG1X-222 is 24V DC and supports RS232 or RS485 communications.
A 12V/24V voltage converter is included.
6. Replaces NEMA 4X polycarbonate enclosure.
7. DC-DC converter included for voltage conversion from 12…24 V DC.
8. If a radio is not selected, antennas and cables cannot be selected.
Code Battery
14 14 Ah
28 28 Ah
56 56 Ah
Cable length between panel
and antenna must not be
longer than 30.5m (100 ft).