User Manual Instruction Manual
Publication 1747-UM655B-EN-P - June 2007
Hardware Setup 43
For additional information about installing the 1747-SDN module, see
the 1747-SDN DeviceNet Scanner Module Installation Instructions,
publication 1747-IN058.
Installing the RediSTATION
Operator Interface
Begin installing the RediSTATION operator interface by removing the
six screws fastening the cover and setting the DIP switches inside.
TIP
You use RSNetWorx for DeviceNet software to configure the
module’s DeviceNet address and communication rate, if
needed. This is done when configuring the DeviceNet network.
See page 52.
DIP Switch Settings
Set this position To this value
1
2
3
4
5
6
1 - On
1 - On
1 - On
0 - Off
0 - Off
0 - Off
Node
Address
(1)
(1)
The DeviceNet address is 000111 (node 7).
7
8
0 - Off
1 - On
Data Rate
(2)
(2)
The data rate is 10 (500 KB). The output fault rate is 0 (outputs turned off). The output
flash rate is 0 (outputs tuned off).
9
10
0 - Off
0 - Off