User Manual Instruction Manual

Publication 1747-UM655B-EN-P - June 2007
Hardware Setup 37
Bank S1 DIP Switches
Switch Setting Position
Switches
1…3
Upper digit
of DF1
station
address
SW1 SW2 SW3 Digit
ON ON ON 0
Switches
4…6
Lower digit
of DF1
station
address
SW4 SW5 SW6 Digit
ON ON ON 0
Switches 7…8 Both OFF
Bank S2 DIP Switches
Switch Setting Position
Switches
1…3
Upper digit
of DF1
station
address
SW1 SW2 SW3 Digit
ON OFF OFF 19200
Switch 4 Full/Half-dup
lex
OFF = Full-duplex
Switch 5 Parity OFF = No parity
Switch 6 Odd/even
parity
Not applicable
Switch 7 Handshake OFF = Hardware handshake disabled
Switch 8 Diagnostic
command
execution
OFF = Disabled
Bank S3 DIP Switches
Switch Setting Position
Switch 1 Duplicate
detect
ON = Duplicate detect on
Switch 2 Error
detect
OFF = CRC error check
Switches
3…4
Number of
retries
SW3 SW4 Number of retries
ON ON 0
Switches
5…8
DF1 ACK
time-out
SW5 SW6 SW7 SW8 Time Out
OFF OFF OFF OFF 3.2