Installation Instructions User guide

1747-SDN DeviceNet Scanner Module 17
Publication 1747-IN058F-EN-P - December 2010
Emissions CISPR 11:
Group 1, Class A (with appropriate enclosure)
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10 V/m with 1 kHz sine-wave 80% AM from 80…2000 Mhz
EFT/B immunity IEC 61000-4-4:
+2 kV at 5 kHz on communication ports
Surge transient immunity IEC 61000-4-5:
±2 kV line-earth(CM) on communications ports
Conducted RF immunity IEC 61000-4-6:
10 Vrms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Magnetic field immunity IEC 61000-4-8
30A/m long duration at 50 Hz
Enclosure type rating None (open style)
Wiring
- Size
- Category
(1)
Refer to DeviceNet Media Design Installation Guide, publication
DNET-UM072
2 — on communication ports
10-pin Linear plug
- Torque
- Catalog number
0.6…0.8 Nm (5…7 lb-in)
1787-PLUG10R
North American temperature code T5
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
.
SLC DeviceNet Scanner — 1747-SDN
Attribute Value