Installation Instructions 1747-SDN DeviceNet Scanner Module Catalog Number 1747-SDN, Series D Topic Page Important User Information 2 Safety Guidelines 2 About the 1747-SDN, Series D DeviceNet Scanner Module 4 Before You Begin 7 Install DeviceNet Scanner Module 9 Interpret the LED Indicators 12 Numeric Codes and Descriptions 14 Specifications 16 Additional Resources 18 Publication 1747-IN058F-EN-P - December 2010
1747-SDN DeviceNet Scanner Module Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices.
1747-SDN DeviceNet Scanner Module 3 Follow these guidelines for environment and enclosure information for this equipment. ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11.
1747-SDN DeviceNet Scanner Module ATTENTION To comply with UL restrictions, this equipment must be powered from a source compliant with the following: Class 2 or Limited Voltage/Current. About the 1747-SDN, Series D DeviceNet Scanner Module The 1747-SDN, Series D module includes these firmware enhancements. • ADR user memory space increased from 64K to 256K • Support added for Online Scanlist Changes in Run Mode.
1747-SDN DeviceNet Scanner Module 5 This feature has the following variations.
1747-SDN DeviceNet Scanner Module Pass-through The SLC 500 pass-through feature allows communication with the DeviceNet network from another network. This feature can be used to adjust and fine tune the nodes on your network. The pass-through feature is not intended to replace a 1770-KFD, 1784-PCD, 1784-PCID, or 1784-PCIDS connection to the network. To use the pass-through feature you must meet the following hardware, software and firmware requirements.
1747-SDN DeviceNet Scanner Module 7 Hardware Features Use this illustration to identify the external features of the scanner module.
1747-SDN DeviceNet Scanner Module For network communication, you have three options. • Use the pass-through feature to communicate with the DeviceNet network from another network. This method is intended for fine tuning and adjustment of network devices. • Use a 1770-KFD RS-232 DeviceNet adapter or 1784-PCD, 1784-PCID, or 1784-PCIDS DeviceNet PC card. This method is necessary for a complete network configuration and real time monitoring of your network devices.
1747-SDN DeviceNet Scanner Module 9 440.646.5800. To install the kit, refer to the ControlFLASH Firmware Upgrade Kit User Manual, publication 1756-QS105. IMPORTANT You can update Series A and B scanner modules up to FRN 7.006. Series C scanner modules support only FRN 8.001 to 8.006. Series D scanner modules support FRN 9.001 and later. Confirm Processor and Adapter Compatibility Make sure that your processor and adapter are compatible.
1747-SDN DeviceNet Scanner Module 3. Insert the module into the slot you have selected. 4. Apply firm, even pressure to seat the module in the I/O chassis backplane connectors. Connect the Module to the DeviceNet Network ATTENTION To comply with the CE Low Voltage Directive (LVD), DeviceNet must be powered from a source compliant with the following: • Safety Extra Low Voltage (SELV) • Protected Extra Low Voltage (PELV).
1747-SDN DeviceNet Scanner Module WARNING 11 If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. 2. Connect the DeviceNet drop line to the 10-pin linear plug by matching the wire insulation colors to the colors shown on the label.
1747-SDN DeviceNet Scanner Module Apply Chassis Power When you apply chassis power, the module numeric indicators cycle through the following displays.
1747-SDN DeviceNet Scanner Module 13 The DeviceNet channel has a bicolor (green/red) network status indicator (NET). The following table provides troubleshooting information about the DeviceNet channel communication link. DeviceNet Channel Communication Indicator Color Description Device Operation Corrective Action Off The channel is disabled for DeviceNet communication.
1747-SDN DeviceNet Scanner Module Numeric Codes and Descriptions Your module uses numeric displays to indicate diagnostic information about the status of your module. The display flashes at 1-second intervals. The following table summarizes the meanings of the numeric codes. Numeric Code Description Corrective Action 0…63 Normal operation. The numeric display indicates the 1747-SDN node address on the DeviceNet network. None. 70 Module failed Duplicate Node Address check.
1747-SDN DeviceNet Scanner Module 15 Numeric Code Description Corrective Action 82 Error detected in sequence of fragmented I/O messages from device. Check scan list table entry for slave device to make sure that input and output data lengths are correct. Check slave device configuration. 83 Slave device is returning error responses when module attempts to communicate with it. Check accuracy of scan list table entry. Check slave device configuration.
1747-SDN DeviceNet Scanner Module Numeric Code Description Corrective Action 98 Unrecoverable firmware failure. Service or replace your module. 99 Unrecoverable hardware failure. Service or replace your module. E2 RAM Test Failure Service or replace your module. E4 Lost power during FLASH upgrade Service or replace your module. E5 No application code Service or replace your module. E9 Module memory has been flushed for factory default settings. Cycle module power to recover.
47-SDN DeviceNet Scanner Module 17 SLC DeviceNet Scanner — 1747-SDN Attribute Value Emissions CISPR 11: Group 1, Class A (with appropriate enclosure) ESD immunity IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000-4-3: 10 V/m with 1 kHz sine-wave 80% AM from 80…2000 Mhz EFT/B immunity IEC 61000-4-4: +2 kV at 5 kHz on communication ports Surge transient immunity IEC 61000-4-5: ±2 kV line-earth(CM) on communications ports Conducted RF immunity IEC 61000-
1747-SDN DeviceNet Scanner Module Certifications - 1747-SDN Certification (when product is Value marked)(1) c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E113724. UL Listed for Class I, Division 2 Group A, B, C, D Hazardous Locations, certified for US and Canada. See UL File E10314.
1747-SDN DeviceNet Scanner Module 19 North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations: Informations sur l’utilisation de cet équipement en environnements dangereux: Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only.
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a . knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.