Manual

Appendix
A
Publication
1747-10.4
Specifications
The table below lists SLC 500 system test specifications.
Description Specification Industry Standard
Operating: 0°C to +60°C (32°F to 140°F) Not Applicable
Storage: –40°C to +85°C (–40°F to 185°F) Not Applicable
Humidity 5 to 95% without condensation Not Applicable
Operating: 1.0G at 5 to 2000 Hz Not Applicable
V
Non-operating: 2.5Gs at 5 to 2000 Hz Not Applicable
Operating: 30.0Gs (3 pulses, 11 ms) Not Applicable
Shock
Operating: 10.0Gs (3 pulses, 11 ms)
Not Applicable
Non-operating: 50.0Gs (3 pulses, 11 ms) Not Applicable
Portable, 2.268 kg (5 lbs) or less at 0.762m
(30 in.) (six drops)
Not Applicable
Portable, 2.268 kg (5 lbs) or more at 0.1016m
(4 in.) (three flat drops)
Not Applicable
Showering Arc: 1.5 kV NEMA ICS 2-230/NEMA ICS 3-304
Surge Withstand Capability: 3 kV IEEE Std. 472-1974/ANSI C37.90/90A-1974
Electromagnetic Compatibility
Fast Transient Burst (impulse): 2 kV for 1746
power supplies, 1kV for 1746 I/O and
communication lines over 10m (32.84 ft), 5 ns
rise time
Internal Rockwell Automation standard
Electrostatic Discharge (ESD): 15 kV,
100 pF/1.5k ohm model
Internal Rockwell Automation standard
Radiated Electromagnetic Susceptibility: 5W
walkie-talkie at 464.5 MHz and 153.05 MHz
Internal Rockwell Automation standard
Dielectric Withstand: 1500V ac UL 508, CSA C22.2 No. 142
Isolation between Communication Circuits:
500V dc
Not Applicable
Isolation between Backplane and I/Os: 1500V
ac
Not Applicable
Flammability and Electrical Ignition: UL94V-0 Not Applicable
Certification
UL listed/CSA approved
Class 1, Groups A, B, C or D, Division 2
CE compliant for all applicable directives
Not Applicable
Internal Rockwell Automation standards are based on Rockwell Automation’s extensive experience in industrial controls.
It is also based partly on industry and/or military specifications.
System Test General