Hardware Style Owner's manual
Chapter 1
Selecting Your Hardware Components
1–7
Output Specifications
The following table details the output specifications for SLC 500 Fixed I/O
Units.
Outputs Specifications
Output Voltage 85-265 VAC
Continuous Current (per output)
0.5 Amp at +30°C
0.25 Amp at +60°C (maximum)
Minimum Load Current 10mA
Triac
Turn-On Time
0.1 milliseconds (maximum)
Triac
Turn-Off Time 10 milliseconds (maximum)
Maximum Off-State Leakage Current 2mA
Maximum On-State Voltage Drop 1.5V @ 0.5 Amps
Maximum Surge Current
10 Amps for 25 milliseconds
➀
Output Voltage 10-50 VDC
Continuous Current (per output)
0.5 Amp at +30°C
0.25 Amp at +60°C (maximum)
Minimum Load Current 1mA
Transistor Sink &
Source
Turn-On Time 0.1 millisecond (maximum)
Source
Turn-Off Time
1 millisecond (maximum)
Maximum Off-State Leakage Current 1mA
Maximum On-State Voltage Drop 1.5V @ 0.5 Amps
Maximum Surge Current
3.0 Amps for 25 milliseconds
➀
Output Voltage Range 5-265 VAC, 5-125 VDC
Continuous Current (per output) 2.5 Amps (maximum)
Continuous Current (per group)
➁
8 Amps (maximum)
Relay
➂
Maximum Load (per chassis) 1440 VA
Relay
➂
Turn-On Time 10 milliseconds (maximum)
Turn-Off Time 10 milliseconds (maximum)
Maximum Off-State Leakage Current 0mA
Minimum Load Current at 5 VDC 10mA
➀
Repeatability is once every 1 second at +30°C. Repeatability is once every 2 seconds at +60°C.
➁
Refer to the wiring diagrams for output groupings on the fixed I/O chassis.
➂
Surge suppression across the output device is recommended to protect relay contacts.