Hardware Style Owner's manual

for Your Fixed Controller
Appendix E
Wiring and Circuit Diagrams and Voltage Ranges
E–42
Output Circuit Diagram
L1
OUT
OUT
Operating Voltage Range
Recommended
Operating Range
0 V
AC
265 V
AC
Operation Not Guaranteed
85 V
AC
Important:
If you measure the voltage at an output terminal that is not connected to a load or is connected to a high-impedance
load, you may measure as much as 100 V
AC even though the output is of
f.