Hardware Style Owner's manual
Appendix A
Setting Up the DH-485 Network
A–13
Grounding and Terminating the DH-485 Network
One (only one) of the link couplers at the end of the link must have
Terminals 1 and 2 of the network connector jumpered together. This
provides an earth ground connection for the shield of the communication
cable.
Link couplers at both ends of the network must have Terminals 5 and 6 of the
link connectors jumpered together. This connects the termination impedance
(of 120Ω) that is built into each link coupler as required by the DH–485
specification. See the figure below for the proper jumpering.
End-of-Line Termination
Belden
#9842 Cable
(1219 m) 4000 ft Maximum
Jumper
Jumper
Jumper
1
2
3
4
5
6
1
2
3
4
5
6