Hardware Style Owner's manual
Appendix A
Setting Up the DH-485 Network
A–11
Connecting the Communication Cable to the Isolated Link Coupler
Attach the terminal block of the link coupler to the Belden #9842 cable as
shown below. Additional terminal blocks are available for replacement, see
chapter 9.
Single Cable Connection
6 Termination
5A
4B
3 Common
2 Shield
1 Chassis Ground
White with Orange Stripes
Orange with White Stripes
Blue with White Stripes
Drain Wire
Shrink Tubing Recommended
Belden #9842
Multiple Cable Connection
to Successive Device
to Previous Device
19525