User Manual
1 Publication 1747-UM010B-EN-P - September 2003
Chapter
5
Configuration and Programming
This chapter contains information necessary to:
• understand remote I/O image files
• understand RIO configuration using G files
• control and view RIO devices using the M0 and M1 files
• understand slot addressing
• quickly configure the RIO Scanner
Understanding Remote
Input and Output Image
Files
The SLC system allows you to assign up to 32 words of input and
output image data to a scanner. This allows your scanner to access a
maximum of four full logical racks (512 input and output points) of
data from remote devices.
The illustration on page 5-2 shows how logical racks, logical groups,
and words are allocated within the I/O image files. Note that this
illustration describes the input image file. The scanner’s output image
file is the same, except that its addressing scheme starts with O:e.O
and ends with O:e.31.