1-20 Overview
Baud Rate Settings
Module Address Switch
The four-position Module Address DIP switch configures the BSN
address in the LSL. The following table shows the address that
corresponds to each setting.
Compatible Devices
The 1747-BSN is compatible with all Remote I/O adapter devices.
Position 1 Position 2 Baud Rate
ON ON 57.6K
ON OFF 115.2K
OFF ON 230.4K
OFF OFF Disabled
Switch Position
1747-BSN Address
1234
OFF OFF OFF
Not Used
1
ON OFF OFF 2
OFF ON OFF 3
ON ON OFF 4
OFF OFF ON 5
ON OFF ON 6
OFF ON ON 7
ON ON ON 8
IMPORTANT
The module address must equal the actual slot
number or the module will fault. For example, the
1747-BSN module in slot 1 must have an address
equal to 1.