User Manual

40 Rockwell Automation Publication 1747-UM076C-EN-E - January 2013
40 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application
7. Click Configuration tab.
The Chunk configuration determines the 1747-AENTR SLC backplane
scan. Set up the chunks as follows:
Output Chunk 1
Size = 8 (number of Output INTs to scan)
File = Output File
Offset = 0 (starting INT offset in Output File)
Output Chunk 2
Size = 64 (number of M0 INTs to scan)
File = M0 File
Offset = 0 (starting INT offset in M0 File)
Output Chunk 3
Size = 0
File = <Don’t Care>
Offset = 0
Input Chunk 1
Size = 8 (number of Input INTs to scan)
File = Input File
Offset = 0 (starting INT offset in Input File)
Input Chunk 2
Size = 64 (number of M1 INTs to scan)
File = M1