User Manual
SLC™ 500 4-Channel Analog I/O Modules 21
Publication 1746-IN008C-EN-P - May 2004
Specifications
General Specifications for NI4, NIO4I, NIO4V, NO4I, NO4V, FIO4I, FIO4V
Description Specification
SLC Communication Format 16-Bit Two’s Complement Binary
Field Wiring to Backplane
Isolation
500V dc
Update Time 512 µs for all channels in parallel
Recommended Cable Shielded Belden #8761
Maximum Wire Size #14 AWG (maximum)
Terminal Block Removable
Location 1746 chassis
Calibration
Factory Calibrated
(1)
(1) For calibrating the 1746-FIO4I and 1746-FI04V analog modules, refer to the customer calibration program and
procedure in the SLC 500 Fast Analog I/O Modules User Manual, publication number 1746-6.9.
Noise Immunity NEMA Standard ICS 2-230
Environmental Conditions
Operating
Temperature
0° to +60° C (+32° to +140° F)
Storage Temperature -40° to +85° C (-40° to +185° F)
Relative Humidity 5 to 95% (non-condensing)
Agency Certification (when
product or packaging is
marked)
N223
Functional Safety 1oo2D (AK 1 to 6, SIL 1 to 3,
according to DIN V 19250 and IEC 61508 respectively)
Category 1 to 4, according to EN954-1
Marked for all applicable directives
Marked for all applicable acts
C-UL Listed Industrial Control Equipment