User Manual
SLC 500™ 32-Channel Digital I/O Modules 7
Publication 1746-IN028A-EN-P - October 2003
Output Module Specifications
Description:
Specification: 1746-
(4)
(4) Series A, B, and C 32-point output modules are fused to protect external wiring, one fuse per common. The fuses are
non-replaceable and are rated at 2.5A. 1746-OB32, OV32 Series D modules are not fused and have a higher current rating
than Series A, B, and C.
OB32 Series D OV32 Series D OB32E
Voltage Category 24
Number of Outputs 32
Points per Common 16
Operating Voltage 5 to 50V dc Source 5-50V dc Sink 10-30V dc Source
Backplane Current
Consumption
5V 0.190A
24V 0A
Isolation from Backplane 1500V ac for 1 min.
Signal Delay (max.) on = 0.1 ms
off = 1.0 ms
on = 1.0 ms
off = 2.0 ms
Off State Leakage (min.) 1 mA
Load Current (min.) 1 mA
Continuous Current per Module (max.)
(1)
(1) To attain the maximum Continuous Current per common rating for an OB32 Series D module, both V dc connections in a wire
group must be connected to your DC source. To attain the maximum Continuous Current per common rating for an OV32
Series D module, both dc Com connections in a wire group must be connected to your DC source.
8.0A at 0°C to 60°C
Continuous Current per Point
(max.)
(1)
at 30°C 0.50A
at 60°C 0.25A
Continuous Current per Common (max.)
(1)
4.0A at 0°C to 60°C
Continuous Current per Common Pin (max.)
(1)
2.0A at 0°C to 60°C
On State Voltage Drop (max.) 1.2V at 0.5A
Surge Current per Point at
30°C
(2)
(2) Repeatability once every second.
1.0A for 10 ms
at
60°C
(3)
(3) Repeatability once every 2 seconds.
1.0A for 10 ms
Electronic Protection No No Yes
Heat Dissipation Watts per Point 0.172 0.172 0.250
Heat Dissipation Watts (min.) 0.95 0.95 0.95
Heat Dissipation Total Watts 6.45 6.45 8.95