User Manual Owner's manual
Publication 1746-UM007C-EN-P - July 2004
8-6 Application Examples
Channel Configuration Worksheet (With Settings Established)
Input Type Select
Data Format Select
Open Circuit Select
Temperature Units Select
Filter Frequency Select
Channel Enable
Not Used
Channel 0
Channel 1
Channel 2
Channel 3
11
1010000
910 8
x
67
00 00
45
0010
0123
0000
0000
0000
Bit Number
(Ambient)
(Bath)
(Steam)
(Chilled
H2O)
101
101
101
x
x
x
00
00
00
00
00
00
0000
0001
0000
12131415
•
•
•
•
•
•
•
Bits:
0-3 Input Type Select 0000 = J
0001 = K
0010 = T
0011 = E
0100 = R
0101 = S
0110 = B
0111 = N
1000 = ±50 mV
1001 = ±100 mV
1111 = CJC temperature
4 and 5 Data Format Select 00 = engineering units, x1 (0.1°/step,
0.01 mV/step)
01 = engineering units, x10 (1°/step,
0.1 mV/step)
10 = scaled-for-PID (0 to 16383)
11 = proportional counts (-32768 to +32767)
6 and 7 Open Circuit Select 00 = zero 01 = upscale 10 = downscale
8 Temperature Units
Select
0 = degrees Celsius 1 = degrees Fahrenheit
9 and 10 Filter Frequency Select 00 = 10 Hz 01 = 50 Hz 10 = 60 Hz 11 = 250 Hz
11 Channel Enable 0 = channel disabled 1 = channel enabled
12-15 Not Used 0000 = always make this setting