User Manual Owner's manual
Publication 1746-UM007C-EN-P - July 2004
Application Examples 8-5
Channel Configuration
Configuration setup for ambient thermocouple:
• channel 0
• type T thermocouple
• display temperature to tenths of a degree
• zero data word in the event of an open circuit
• 60 Hz input filter to provide 60 Hz line noise rejection
Configuration setup for bath thermocouple:
• channel 1
• type J thermocouple
• display temperature to tenths of a degree
• zero data word in the event of an open circuit
• 60 Hz input filter to provide 60 Hz line noise rejection
Configuration setup for steam thermocouple:
• channel 2
• type K thermocouple
• display temperature to tenths of a degree
• zero data word in the event of an open circuit
• 60 Hz input filter to provide 60 Hz line noise rejection
Configuration setup for chilled H
2
O thermocouple:
• channel 3
• type J thermocouple
• display temperature to tenths of a degree
• zero data word in the event of an open circuit
• 60 Hz input filter to provide 60 Hz line noise rejection
Configuration setup for cabinet temperature:
• channel 0
• CJC temperature
• display temperature to tenths of a degree
• zero data word in the event of an open circuit
• 60 Hz input filter to provide 60 Hz line noise rejection