User Manual Owner's manual

Publication 1746-UM007C-EN-P - July 2004
Application Examples 8-5
Channel Configuration
Configuration setup for ambient thermocouple:
channel 0
type T thermocouple
display temperature to tenths of a degree
zero data word in the event of an open circuit
60 Hz input filter to provide 60 Hz line noise rejection
Configuration setup for bath thermocouple:
channel 1
type J thermocouple
display temperature to tenths of a degree
zero data word in the event of an open circuit
60 Hz input filter to provide 60 Hz line noise rejection
Configuration setup for steam thermocouple:
channel 2
type K thermocouple
display temperature to tenths of a degree
zero data word in the event of an open circuit
60 Hz input filter to provide 60 Hz line noise rejection
Configuration setup for chilled H
2
O thermocouple:
channel 3
type J thermocouple
display temperature to tenths of a degree
zero data word in the event of an open circuit
60 Hz input filter to provide 60 Hz line noise rejection
Configuration setup for cabinet temperature:
channel 0
CJC temperature
display temperature to tenths of a degree
zero data word in the event of an open circuit
60 Hz input filter to provide 60 Hz line noise rejection