8-2 Application Examples
Channel Configuration
Configure the thermocouple channel with the following setup:
type J thermocouple
°F - display to whole degree
zero data word in the event of an open circuit
10 Hz input filter to reject high frequency noise and give good
rejection of 60 Hz line noise
Channel Configuration Worksheet (With Settings Established for Channel 0)
Input Type Select
Data Format Select
Open Circuit Select
Temperature Units Select
Filter Frequency Select
Channel Enable
Not Used
Channel
0
Channel 1
Channel 2
Channel 3
11
0010000
910 8
1
67
00 01
45
0000
0123
0000
0000
0000
Bit Number
12131415
Bits:
0-3 Input Type Select 0000 = J
0001 = K
0010 = T
0011 = E
0100 = R
0101 = S
0110 = B
0111 = N
1000 = ±50 mV
1001 = ±100 mV
1111 = CJC temperature
4 and 5 Data Format Select 00 = engineering units, x1 (0.1°/step,
0.01 mV/step)
01 = engineering units, x10 (1°/step,
0.1 mV/step)
10 = scaled-for-PID (0 to 16383)
11 = proportional counts (-32768 to +32767)
6 and 7 Open Circuit Select 00 = zero 01 = upscale 10 = downscale
8 Temperature Units
Select
0 = degrees Celsius 1 = degrees Fahrenheit
9 and 10 Filter Frequency Select 00 = 10 Hz 01 = 50 Hz 10 = 60 Hz 11 = 250 Hz
11 Channel Enable 0 = channel disabled 1 = channel enabled
12-15 Not Used 0000 = always make this setting