User Manual Owner's manual

Publication 1746-UM007C-EN-P - July 2004
5-14 Channel Configuration, Data, and Status
Bit(s) Define These bit settings Indicate this
1514131211109876543210
0–3 Input type 0 0 0 0 Thermocouple Type J
0 0 0 1 Thermocouple Type K
0 0 1 0 Thermocouple Type T
0 0 1 1 Thermocouple Type E
0 1 0 0 Thermocouple Type R
0 1 0 1 Thermocouple Type S
0 1 1 0 Thermocouple Type B
0 1 1 1 Thermocouple Type N
100050 mV
1 0 0 1 100 mV
1 0 1 0 Invalid
1 0 1 1 Invalid
1 1 0 0 Invalid
1 1 0 1 Invalid
1 1 1 0 Invalid
1 1 1 1 CJC temperature
4 and 5
Data type 1
00
Engineering units x 1
(2)
01
Engineering units x 10
(2)
1 0 Scaled–for–PID
1 1 Proportional Counts
6 and 7 Open circuit type 0 0 Zero
0 1 Upscale
10 Downscale
1 1 Invalid
8 Temperature units
type
(1)
0 Degrees C
1 Degrees F
9 and 10 Channel filter
frequency
0 0 10 Hz
0 1 50 Hz
1 0 60 Hz
1 1 250 Hz
11 Channel status 0 Channel Disabled
1 Channel Enabled
12 Open–circuit error 0 No error
1 Open circuit detected
13 Under–range error 0 No error
1 Under–range condition
14 Over–range error 0 No error
1 Over–range condition
15 Configuration error 0 No error
1 Configuration error
(1) When millivolt input type is selected, the bit setting for temperature units is ignored.
(2) For engineering units x1, values are expressed in 0.1 degrees or 0.01 mV. For engineering units x10, values are expressed in 1.0 degrees or 0.1 mV.